• There are no items in your cart

ASTM E 1966 : 2015

Superseded

Superseded

A superseded Standard is one, which is fully replaced by another Standard, which is a new edition of the same Standard.

View Superseded by
superseded

A superseded Standard is one, which is fully replaced by another Standard, which is a new edition of the same Standard.

Standard Test Method for Fire-Resistive Joint Systems

Available format(s)

Hardcopy , PDF

Superseded date

03-21-2019

Language(s)

English

Published date

06-01-2015

This test method measures cut resistance of garments and devices worn to protect the lower body (legs) when operating a chainsaw.2

1.1This fire-test-response test method measures the performance of joint systems designed to be used with fire rated floors and walls during a fire endurance test exposure. The fire endurance test end point is the period of time elapsing before the first performance criteria is reached when the joint system is subjected to one of two time-temperature fire exposures.

1.2The fire exposure conditions used are either those specified by Test Method E119 for testing assemblies to standard time-temperature exposures or Test Method E1529 for testing assemblies to rapid-temperature rise fires.

1.3This test method specifies the heating conditions, methods of test, and criteria for the evaluation of the ability of a joint system to maintain the fire resistance where hourly rated fire-separating elements meet.

1.4Test results establish the performance of joint systems during the fire-exposure period and shall not be construed as having determined the joint systems suitability for use after that exposure.

1.5This test method does not provide quantitative information about the joint system relative to the rate of leakage of smoke or gases or both. However, it requires that such phenomena be noted and reported when describing the general behavior of joint systems during the fire endurance test but is not part of the conditions of compliance.

1.6Potentially important factors and fire characteristics not addressed by this test method include, but are not limited to:

1.6.1The performance of the fire-resistive joint system constructed with components other than those tested.

1.6.2The cyclic movement capabilities of joint systems other than the cycling conditions tested.

1.7The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and are not considered standard.

1.8The text of this standard references notes and footnotes which provide explanatory material. These notes and footnotes (excluding those in tables and figures) shall not be considered as requirements of the standard.

1.9This standard is used to measure and describe the response of materials, products, or assemblies to heat and flame under controlled conditions, but does not by itself incorporate all factors required for fire hazard or fire risk assessment of the materials, products, or assemblies under actual fire conditions.

1.10Fire testing is inherently hazardous. Adequate safeguards for personnel and property shall be employed in conducting these tests.

1.11This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.

Committee
E 05
DocumentType
Test Method
Pages
16
PublisherName
American Society for Testing and Materials
Status
Superseded
SupersededBy
Supersedes

ASTM E 2393 : 2010 : REV A : R2015 Standard Practice for On-Site Inspection of Installed Fire Resistive Joint Systems and Perimeter Fire Barriers
ASTM E 2837 : 2013 : R2017 Standard Test Method for Determining the Fire Resistance of Continuity Head-of-Wall Joint Systems Installed Between Rated Wall Assemblies and Nonrated Horizontal Assemblies
ASTM E 2874 : 2019 Standard Test Method for Determining the Fire-Test Response Characteristics of a Building Spandrel-Panel Assembly Due to External Spread of Fire
ASTM E 3157 : 2019 Standard Guide for Understanding and Using Information Related to Installation of Firestop Systems
ASTM E 2750 : 2017 Standard Guide for Extension of Data from Penetration Firestop System Tests Conducted in Accordance with ASTM E814
ASTM E 3038 : 2016 Standard Practice for Assessing and Qualifying Candidates as Inspectors of Firestop Systems and Fire-Resistive Joint Systems
ASTM E 3134 : 2017 Standard Specification for Transportation Tunnel Structural Components and Passive Fire Protection Systems
ASTM F 2021 : 2017 Standard Guide for Design and Installation of Plastic Siphonic Roof Drainage Systems
ASTM E 2912 : 2017 Standard Test Method for Fire Test of Non-Mechanical Fire Dampers Used in Vented Construction
ASTM E 2307 : 2019 Standard Test Method for Determining Fire Resistance of Perimeter Fire Barriers Using Intermediate-Scale, Multi-story Test Apparatus
ASTM E 2226 : 2015 : REV B : R2019 Standard Practice for Application of Hose Stream
ASTM E 2749 : 2015 : REV A : R2019 Standard Practice for Measuring the Uniformity of Furnace Exposure on Test Specimens

View more information
US$83.00
Excluding Tax where applicable

Access your standards online with a subscription

Features

  • Simple online access to standards, technical information and regulations.

  • Critical updates of standards and customisable alerts and notifications.

  • Multi-user online standards collection: secure, flexible and cost effective.