• There are no items in your cart

BS EN 61558-2-6:2009

Current
Current

The latest, up-to-date edition.

Safety of transformers, reactors, power supply units and similar products for supply voltages up to 1100 V Particular requirements and tests for safety isolating transformers and power supply units incorporating safety isolating transformers
Available format(s)

Hardcopy , PDF

Language(s)

English

Published date

01-31-2010

1 Scope
2 Normative references
3 Terms and definitions
4 General requirements
5 General notes on tests
6 Ratings
7 Classification
8 Marking and other information
9 Protection against electric shock
10 Change of input voltage setting
11 Output voltage and output current under load
12 No-load output voltage
13 Short-circuit voltage
14 Heating
15 Short-circuit and overload protection
16 Mechanical strength
17 Protection against harmful ingress of dust,
   solid objects and moisture
18 Insulation resistance, dielectric strength and
   leakage current
19 Construction
20 Components
21 Internal wiring
22 Supply connection and other external flexible
   cable or cords
23 Terminals for external conductors
24 Provisions for protective earthing
25 Screws and connections
26 Creepage distances, clearances and distances
   through insulation
27 Resistance to heat, fire and tracking
28 Resistance to rusting
Annexes
Annex C - Creepage distances (cr), clearances (cl)
          and distances through insulation (dti)
          Material group II (400 <= CTI < 600)
Annex D - Creepage distances (cr), clearances (cl)
          and distances through insulation (dti)
          Material group I (CTI >= 600)
Annex R - Explanations of the application of 4.2 of
          IEC 60664-1:2007
Bibliography
Annex ZA (normative) - Normative references to
         international publications with their
         corresponding European publications

Specifies the safety of safety isolating transformers for general applications and power supply units incorporating safety isolating transformers for general applications. Transformers incorporating electronic circuits are also covered by this standard.

Replacement:

This part of IEC 61558 deals with the safety of safety isolating transformers for general applications and power supply units incorporating safety isolating transformers for general applications. Transformers incorporating electronic circuits are also covered by this standard.

NOTE 1 Safety includes electrical, thermal and mechanical aspects.

Unless otherwise specified, from here onward, the term transformer covers safety isolating transformers for general applications and power supply units incorporating safety isolating transformers for general applications.

NOTE 2 For power supply units (linear) this part is applicable. For switch mode power supply units, IEC 61558-2-16 is applicable together with this part.

This part is applicable to stationary or portable, single-phase or polyphase, air-cooled (natural or forced) independent or associated dry- type transformers. The windings may be encapsulated or non-encapsulated.

The rated supply voltage does not exceed 1 100 V a.c., and the rated supply frequency and the internal operating frequencies do not exceed 500 Hz.

The rated output does not exceed:

  • 10 kVA for single-phase transformers;

  • 16 kVA for polyphase transformers.

This part is applicable to transformers without limitation of the rated output subject to an agreement between the purchaser and the manufacturer.

NOTE 3 Transformers intended to supply distribution networks are not included in the scope.

The no-load output voltage or the rated output voltage does not exceed 50 V a.c. or 120 V ripple-free d.c.

This part is not applicable to external circuits and their components intended to be connected to the input terminals and output terminals of the transformers.

Transformers covered by this part are used in applications where double or reinforced insulation between circuits is required by the installation rules or by the end product standard.

NOTE 4 Attention is drawn to the following:

  • for transformers intended to be used in vehicles, on board ships, and aircraft, additional requirements (from other applicable standards, national rules, etc.) may be necessary;

  • measures to protect the enclosure and the components inside the enclosure against external influences such as fungus, vermin, termites, solar-radiation, and icing should also be considered;

  • the different conditions for transportation, storage, and operation of the transformers should also be considered;

  • additional requirements in accordance with other appropriate standards and national rules may be applicable to transformers intended for use in special environments.

NOTE 5 Future technological development of transformers may necessitate a need to increase the upper limit of the frequencies, until then this part may be used as a guidance document.

Committee
PEL/96
DevelopmentNote
Supersedes BS EN 60742 and BS 3535-1(1996) Supersedes 94/201278 DC (11/2005) To be read in conjunction with BS EN 61558-1. Supersedes 06/30158173 DC. (01/2010)
DocumentType
Standard
Pages
18
PublisherName
British Standards Institution
Status
Current
Supersedes

Standards Relationship
IEC 61558-2-6:2009 Identical
UNE-EN 61558-2-6:2010 Identical
NF EN 61558-2-6 : 2009 Identical
DIN EN 61558-2-6 : 2010 Identical
I.S. EN 61558-2-6:2009 Identical
SN EN 61558-2-6 : 1997 Identical
EN 61558-2-6:2009 Identical

BS 7909:2011 Code of practice for temporary electrical systems for entertainment and related purposes
BS 7671(2008) : 2018 REQUIREMENTS FOR ELECTRICAL INSTALLATIONS - IET WIRING REGULATIONS
BIP 2081 : 2012 A GUIDE TO EMERGENCY LIGHTING
BS 7909:2008 CODE OF PRACTICE FOR TEMPORARY ELECTRICAL SYSTEMS FOR ENTERTAINMENT AND RELATED PURPOSES
BS 7375:2010 Distribution of electricity on construction and demolition sites. Code of practice
BS 7671(2008) : 2008 REQUIREMENTS FOR ELECTRICAL INSTALLATIONS - IET WIRING REGULATIONS

EN 61558-1:2005/A1:2009 SAFETY OF POWER TRANSFORMERS, POWER SUPPLIES, REACTORS AND SIMILAR PRODUCTS - PART 1: GENERAL REQUIREMENTS AND TESTS
IEC 61558-2-16:2009+AMD1:2013 CSV Safety of transformers, reactors, power supply units and similar products for supply voltages up to 1 100 V - Part 2-16: Particularrequirements and tests for switch mode power supply units andtransformers for switch mode power supply units
IEC 61558-1:2017 Safety of transformers, reactors, power supply units and combinations thereof - Part 1: General requirements and tests

View more information
US$160.51
Excluding Tax where applicable

Access your standards online with a subscription

Features

  • Simple online access to standards, technical information and regulations.

  • Critical updates of standards and customisable alerts and notifications.

  • Multi-user online standards collection: secure, flexible and cost effective.