• There are no items in your cart

IEEE DRAFT C37.63 : D5 95

Superseded
Superseded

A superseded Standard is one, which is fully replaced by another Standard, which is a new edition of the same Standard.

View Superseded by
superseded

A superseded Standard is one, which is fully replaced by another Standard, which is a new edition of the same Standard.

STANDARD REQUIREMENTS FOR OVERHEAD, PAD-MOUNTED, DRY-VAULT, AND SUBMERSIBLE AUTOMATIC LINE SECTIONALIZERS FOR AC SYSTEMS
Superseded date

09-15-1997

Published date

01-12-2013

SECTION
1. Scope
2. References
3. Service Conditions
 3.1 Usual Service Conditions
 3.2 Other Conditions that may affect Design and
      Application
4. Definitions
5. Rating
 5.1 Rating Information
 5.2 Rated maximum Voltage
 5.3 Rated Frequency
 5.4 Rated Continuous Current
      5.4.1 Conditions of Continuous Current Rating
      5.4.2 Limits of Observable Temperature Rise
             5.4.2.1 Classification of Insulating
                       Materials
 5.5 Rated Minimum Actuating Current
 5.6 Rated Symmetrical Interrupting (Load current
      switching) Current (Manual operation only)
 5.7 Rated Marking Current
 5.8 Rated Momentary Current
 5.9 Rated 1 s Current
 5.10 Rated 10 s Current
 5.11 Rated Dielectric Withstand Voltage
 5.12 Overload Rating
 5.13 Rated control voltage and Ranges
 5.14 Rated Cable Charging Interrupting Current (where
      applicable)
6. Design Tests
 6.1 General
      6.1.1 Condition of Device to be Tested
      6.1.2 Mounting of Device
      6.1.3 Grounding Device
      6.1.4 Frequency
      6.1.5 Control Voltage
 6.2 Insulation (Dielectric tests)
      6.2.1 Withstand Test Voltage
      6.2.2 Electrical Connections
      6.2.3 Points of Application of Test Voltage
      6.2.4 Temperature
      6.2.5 Dielectric Test Procedures and Voltage
             Measurements
 6.3 Interrupting Tests
      6.3.1 Load Current Interrupting Tables
             6.3.1.1 Test Conditions
             6.3.1.2 Test Procedure
      6.3.2 Cable Charging Current Interrupting Test
             6.3.2.1 Test Conditions
             6.3.2.2 Test Procedure
             6.3.2.3 Performance
      6.3.3 Transformer Magnetizing Current Interruption
             Test
             6.3.3.1 Test Conditions
             6.3.3.2 Test Procedure
             6.3.3.3 Performance
 6.4 Standard Operating Duty Tests
      6.4.1 Operating Duty Tests for Load Interrupting
             Sectionalizers
      6.4.2 Operating Duty Tests for Nonload
             Interrupting Sectionalizers
      6.4.3 Operating Performance
      6.4.4 Condition After Standard Operating Duty
             Tests
      6.4.5 Interpretation of Standard Operating Duty
             Tests
 6.5 Making and Momentary Current tests
 6.6 Minimum Actuating Current Tests
      6.6.1 Test Circuit
      6.6.2 Test Procedure
 6.7 Partial Discharge Tests
 6.8 Radio Influence Voltage (RIV) Tests
      6.8.1 Test Voltages and Limits
      6.8.2 Test Conditions
             6.8.2.1 Proximity of Other Apparatus
             6.8.2.2 Oil-Filled Sectionalizers
             6.8.2.3 Electrical Connections
             6.8.2.4 Ambient Radio Noise
             6.8.2.5 Atmospheric Conditions
      6.8.3 Test Equipment and Procedure
             6.8.3.1 Procedure
             6.8.3.2 Tests on Multipole Devices
             6.8.3.3 Tests on Assembled Apparatus
             6.8.3.4 Precautions
 6.9 Short-Time Current Tests
      6.9.1 Determination of 1 s and 10 s Currents
      6.9.2 Condition After Test
 6.10 Surge Current Test-Series Coil Sectionalizers
      6.10.1 Test Conditions
      6.10.2 Test Procedure
      6.10.3 Condition After Test
 6.11 Temperature Rise Test
      6.11.1 Test Conditions
      6.11.2 Electrical Conditions
      6.11.3 Test Procedure
             6.11.3.1 Method of Temperature Determination
             6.11.3.2 Value of Ambient Temperature During
                      Test
             6.11.3.3 Determination of the Ambient
                      Temperature
             6.11.3.3.1 Placing of Thermocouples
             6.11.3.3.2 Use of Oil Cup
 6.12 Mechanical Operation Test
      6.12.1 Mechanical Duty test
      6.12.2 Cold Temperature Test
 6.13 Control Elements Surge Withstand Capability Tests
      6.13.1 Oscillatory Surge Tests
             6.13.1.1 Test Procedure
      6.13.2 Simulated Surge Arrester Operation Test
             6.13.2.1 Test Procedure
      6.13.3 Condition of Control During and after Test
7. Production Tests
 7.1 Counting and Overcurrent Trip Calibration
 7.2 Control, Secondary Wiring, and Accessory Devices
      Check Tests
 7.3 Dielectric Withstand Test-1 min Dry Power
      Frequency
 7.4 Mechanical Operation Tests
 7.5 Leak Test
8. Construction Requirements
 8.1 Tank Construction
 8.2 Grounding Provisions
 8.3 Insulating Medium Quantity Indicators (Submersible
      sectionalizers)
 8.4 Oil Sampling Provisions (Submersible
      Sectionalizers)
 8.5 Manual Operating Provision
      8.5.1 Submersible or Dry-Vault Sectionalizer
      8.5.2 Pad-Mounted Sectionalizers
 8.6 Position Indicator
 8.7 Nameplate Markings
 8.8 Stored Energy Mechanism Charge Indicator
 8.9 Separate Mounting of Control Apparatus
 8.10 Counters
 8.11 Conductor Terminal Sizes
 8.12 Vacuum Interrupters
9. Application Considerations
 9.1 Unusual Service Conditions
 9.2 Safety Provisions
FIGURES
Fig 1 Load Current Switching Interrupting Circuits (a)
      Three-Phase Circuit (b) Single-Phase Test Circuit
Fig 2 Cable Charging Current Interrupting Test Circuit
Fig 3 Magnetizing Current Test Circuits (a) Test Circuit
      Wye Connected (b) Test Circuit-Delta Connected
Fig 4 Surge Withstand Test Circuits-Control (a) Control
      Element with Sectionalizer (b) Control with
      Transformer.
TABLES
Table 1 Preferred Ratings & Performance Characteristics
         of Automatic Line Sectionalizers
Table 2 Preferred Ratings of Automatic Line
         Sectionalizers
Table 3A Temperature Limits for Insulating Materials as
         used in Automatic Line sectionalizers
Table 3B Temperature Limits for Contacts, Conducting
         Joints, or Bushing Terminals when clean and
         bright as used in Automatic Line
         Sectionalizers
Table 4 Rated Control Voltages and Ranges for
         Sectionalizers
Table 5 Preferred Cable Charging Interrupting Current
         Ratings
Table 6 Test Voltages and Limits of Conducted Radio
         Influence Voltage
Table 7 Size of Bare Copper Leads
Table 8 Size of Aluminium Cable Leads
Table 9 Altitude Correction Factors

Applies to all overhead, pad mounted, dry-vault, and submersible single or multi-pole alternating current automatic line sectionalizers for rated maximum voltages above 1000 V ac.

DocumentType
Draft
PublisherName
Institute of Electrical & Electronics Engineers
Status
Superseded
SupersededBy

IEEE 386-2016 REDLINE IEEE Standard for Separable Insulated Connector Systems for Power Distribution Systems Rated 2.5 kV through 35 kV
IEEE 4-2013 IEEE Standard for High-Voltage Testing Techniques
IEEE C37.09-1999 IEEE Standard Test Procedure for AC High-Voltage Circuit Breakers Rated on a Symmetrical Current Basis
IEEE C37.24-2003 IEEE Guide for Evaluating the Effect of Solar Radiation on Outdoor Metal-Enclosed Switchgear

View more information
Sorry this product is not available in your region.

Access your standards online with a subscription

Features

  • Simple online access to standards, technical information and regulations.

  • Critical updates of standards and customisable alerts and notifications.

  • Multi-user online standards collection: secure, flexible and cost effective.